This guide helps you to carry out the various calculations required to define and determine network characteristics, substation equipment dimensions and provides useful information enabling you to design your MV switchboard and other substation devices.

Exercise sections and answers //

  1. MV substation architectures
  2. MV substation architectures
  3. Industrial C13-200 MV substation
  4. Max. distance between surge arrester and MV equipment
  5. Calculation of MV cable cross-section
  6. Calculation of Isc
  7. CT s for MV metering
  8. CT s for MV protection
  9. Earth-fault relay settings
  10. Capacitors

Exercise 1 – MV substation architectures

To define //

  1. Type of LV or MV metering
  2. Architecture and choice of cubicles
  3. Type and rating of fuse that protects the transformer

Inputs //

  • Consumer substation on energy supplier loop: 20kV
  • 1 800kVA transformer with 20kV/400V secondary
  • Short-circuit power 250 MVA

Answers and chosen substation equipment //

  • 800 kVA with 20 kV = 23A < 45A
    OK for LV metering
  • 800 kVA with 410V = 1127A < 2000A
  • 800 kVA < 1250 kVA
  • MV Isc 20kV = 250MVA / 20kV / 1.732 = 7.2 kA rms
    OK for standard equipment 24 KV 12.5 kA
  • 800 kVA 20 kV transformer, UTE standard,
    43A Solefuse chosen fuse rating
Chosen MV substation architecture
Chosen MV substation architecture

Title:MV Network Design Answer and Exercise Book by Schneider Electric
Format:PDFs
Size:100 KB + 170 KB
Pages:31 + 37
Download 1:Right here
Download 2:Right here | Get Download Updates | Get Technical articles
MV Network Design - Answer and Exercise Book
MV Network Design – Answer and Exercise Book by Schneider Electric

SEARCH: Articles, software & guides

Premium Membership

Premium membership gives you an access to specialized technical articles and extra premium content (electrical guides and software).
Get Premium Now ⚡

Page edited by E.C. (Google).

One Comment


  1. Jason
    May 02, 2016

    Where is the Design Guide? The only downloads I see are for the exercise book and the answer book, but not the actual guide.

Leave a Comment

Tell us what you're thinking... we care about your opinion!

Premium Membership

Get access to premium electrical guides, technical articles and much more!