Current transformers or CTs take up a lot of space in HV cubicles. Through knowledge of how they work makes it possible to:

  • Reduce their dimensions and thus their cost,
  • Use standard CTs in a larger number of configurations.

The purpose of this study is to learn more about CT operation in association with protection relays and to lay down a few rules for sizing them properly. After a brief theoretical review of CT operation and current protection devices, the behaviour of the CTprotection relay combination is studied in two particularly important cases
in HV:

  • overcurrent relay supplied by a heavily saturated CT,
  • protection relay connected to two CTs in parallel in duplex cubicles.

This study is completed by experimental results.

Theoretical Review

Current transformers consist of a magnetic circuit in toroid form. The primary is made up of n1 turns or simply a single conductor crossing the toroid (n1 = 1). The secondary is wound in n2 regular turns around this toroid (see fig. 1 and 2).
Ampere’s theorem states that the sum of the ampere-turns is equal to the circulation of the magnetic field vector.

AUTHOR: Schneider Electric expert | Michel ORLHAC

Title:Current transformers for HV protection
Download:Right here | Get Download Updates | Get Technical articles

Current transformers for HV protection

SEARCH: Articles, software & guides

Premium Membership

Premium membership gives you an access to specialized technical articles and extra premium content (electrical guides and software).
Get Premium Now ⚡

Page edited by E.C. (Google).

One Comment

  1. Mustafa assal
    Dec 19, 2011


Leave a Comment

Tell us what you're thinking... we care about your opinion!

Premium Membership

Get access to premium electrical guides, technical articles and much more!