Transmission And Distribution Electrical Engineering
Transmission And Distribution Electrical Engineering

Load Flow

A load flow analysis allows identification of real and reactive power flows, voltage profiles, power factor and any overloads in the network. Once the network parameters have been entered into the computer database the analysis allows the engineer to investigate the performance of the network under a variety of outage conditions.

The effect of system losses and power factor correction, the need for any system reinforcement and confirmation of economic transmission can then follow.


Network single-line diagram

Figure 1.1 shows a simple five busbar 6 kV generation and 33 kV distribution network for study. Table 1.1 details the busbar and branch system input data associated with the network. Input parameters are given here in a per unit (pu) format on a 100MVA base. Different programs may require input data in different formats, for example per cent impedance, ohmic notation, etc.

The network here is kept small in order to allow the first-time user to become rapidly familiar with the procedures for load flows. Larger networks involve a repetition of these procedures.

Title:Transmission and Distribution Electrical Engineering By Colin Bayliss, Brian Hardy
Format:PDF
Size:17.3MB
Pages:1010
Download:Right here | Get Download Updates | Get Technical articles
Transmission And Distribution Electrical Engineering
Transmission And Distribution Electrical Engineering

SEARCH: Articles, software & guides

Premium Membership

Premium membership gives you an access to specialized technical articles and extra premium content (electrical guides and software).
Get Premium Now ⚡

Page edited by E.C. (Google).

16 Comments


  1. José Zerpa
    May 27, 2015

    Hello. You can download of the website http://www.academia.edu free. Regards.


  2. James McConnell
    Apr 17, 2015

    Still can’t find the link! Any clues?


  3. NT
    Apr 06, 2015

    Hello. Is it possible to download this guide for free?


  4. Roger Chua
    Apr 05, 2015

    hello i think the download link is wrong. led me to a google page

    • Edvard
      Edvard
      Apr 06, 2015

      It’s not a mistake. But, there is another link where you can download guide ;)


      • Edmund Ray
        Jul 22, 2015

        where Sir?

Leave a Comment

Tell us what you're thinking... we care about your opinion!

Premium Membership

Get access to premium electrical guides, technical articles and much more!