Purpose of Design manual //

This manual is a guide for electrical and telecommunications engineers and designers (hereafter referred as A/E) for the planning and design of the electrical power distribution, lighting, signal, telecommunications, and related systems (hereinafter referred to as systems).

It is expected that systems designed with the use of this manual shall meet their primary objective of providing a safe, reliable, and energy efficient installation.

In order to provide the latitude needed for new technologies and concepts, technical deviations from the stipulations of this manual may be made only if a safe, reliable, and energy-efficient design shall result.


Grounding //

Provide a copper bus plate minimum 6 in x 18 in x 0.5 in [150 mm x 450 mm x 13 mm], with a connection point located on the inside wall within the immediate area of the antenna coaxial cable(s) entrance conduit sleeves.

Connect this plate to the lightning protection system with a minimum #1/0 AWG stranded copper wire, or increased sized connection device (i.e., strap, buss, etc.) as approved by the RE, to maintain the integrity of the lightning protection system so each of the system antenna cables’ coaxial cable lightning protectors can be installed and connected to the plate.

Single or multiple mission critical buildings, standby and essential electrical system generators at energy center
Single or multiple mission critical buildings, standby and essential electrical system generators at energy center

Title: Electrical Design Manual For Hospitals – Office of Construction & Facilities Management Facilities Quality Service
Format: PDF
Size: 3.5 MB
Pages: 126
Download: Right here | Get Download Updates | Get Technical articles
Electrical Design Manual For New Hospitals
Electrical Design Manual For New Hospitals

SEARCH: Articles, software & guides

Premium Membership

Premium membership gives you an access to specialized technical articles and extra premium content (electrical guides and software).
Get Premium Now ⚡

Page edited by E.C. (Google).

6 Comments


  1. Vicente Martinez
    Jun 20, 2016

    thank you for so many technical artículos


  2. Raoul Desir
    Mar 24, 2016

    Hello Edvard , can you give me a link where I can download autocad electrical for free , thanks in advance


  3. Eng. Gemunu Wijegunawardana.
    Mar 12, 2014

    Very good technical specification for hospitals. But, I haven’t come across isolating transformers ( mainly for operating theaters) please elaborate and comment.
    Best regards.


  4. Dr. Eng. Ihsan Bawadekji
    Dec 06, 2013

    Dear Sirs,
    I want to guide me for some body can give me a permission to translate this book.
    Best Regards,


    • deGraft Johnson Isaac Ekow
      Apr 06, 2016

      Hello Edvard
      I am also interested if you can you give me a link where I can download autocad electrical for free , thanks in advance.

      I have been enjoying the technical papers here in Ghana. I wish I can run continues professional program here in Ghana with your documents. It is interesting what we read from here are not in class room and in country where there is no continues training and program, it is difficult for the next generation to develop.


  5. Ashvin Patel
    Dec 06, 2013

    Good technical details.

Leave a Comment

Tell us what you're thinking... we care about your opinion!

Premium Membership

🔌 Get access to premium electrical guides, technical articles and much more!